Shunt Powerline Protection
ILSE offers a wide selection of technologies and products which are available for transient protection of the mains power supply at the point of entry to your facility. These products / technologies are represented in two categories shunt protection and series protection.
- Ideal for robust equipment such as air conditioning, pumps and motors
- Point of entry protection
- Energy diversion only, voltage clamping devices installed between each phase and neutral or earth on mains switch board
Class I Protectors, (Spark Gap based) per IEC 61643
![]() |
|
Class II Protectors, (MOV based) per IEC 61643
![]() |
|
Series Powerline Protection
Series powerline protection is the best available protection for sensitive electronics such as rectifiers, switchmode power supplies, and other mission critical equipment. The Series Filter reduces the rate of rise of any transient overvoltage to acceptable levels, and also reduces the overall magnitude of the transient voltage the equipment receives.
Low Current Single Phase Filters
Location: IEC 61643 Class III
![]() |
|
Single and Three Phase Surge Filters
Location: IEC 61643 Class I, II & III
Standard Surge Filter Order code:
SF X YY A-NE
Where X is number of phases, and YY is circuit current rating per phase.
Other voltages available on request.
Standard Surge Filter specifications:
All units can withstand overvoltage and fault conditions in accordance with IEC 61643 requirements. All units incorporate non saturating inductors combined with high reliability capacitors to form an effective low pass filter, incorporating shunt protection elements on the line and load sides.
Number of Phases X | Current Rating YY | Description |
1 or 3 | 32A,63A | Surge filter with Class II protection applied P-N, 100kA 8/20µs line side protection, 50kA 8/20µs load side protection per phase. 100kA 10/350µs N-E |
1 or 3 | 125A,200A | Surge filter with Class I protection applied P-N, 50kA 10/350µs, 135kA 8/20µs line side protection, 50kA 8/20µs load side protection per phase.100kA 10/350µs N-E |
3 | 315A,400A 630A,800A 1000A,1250A |
Surge filter with Class I protection applied P-N, 50kA 10/350μs, 135kA 8/20μs line side protection, 50kA 8/20μs load side protection per phase.100kA 10/350μs N-E |